Motor protections
Note on protections
81 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Protection
Trip time t
[ANSI code]
R JAM [51LR]
t
= tj
t
R STALL [51LR]
t
= ts
t
UC [37]
t
= tuc
t
U
t
= tu
(8)
t
(1)
use trip and threshold current values expressed in In for calculating t
(2)
with t4 = instantaneous, the maximum tolerance is 50 ms
(3)
Tolerance values valid with Trip unit at steady state or on with auxiliary power supply, trip time ≥ 100 ms,
temperature and signals within operating limits; the tolerances in the table after the notes are applicable if the
conditions are not guaranteed
(4)
the trip unit considers a 3% hysteresis for clearing from the alarm condition
(5)
tolerance valid for frequencies within range: fn ± 2 %. A ± 5% tolerance is applicable for off range
frequencies
(6)
± 20% for threshold 0.4 Hz / s
(7)
time to be considered valid after Motor start-up
(8)
time to be considered valid with protection in alarm status after Motor start-up; if the alarm appears during
Motor start-up, the trip unit calculates and uses the lowest value between tu and the half of Motor start-up
Performance guaranteed in all operating conditions
Protection
Trip threshold tolerance
L
Activation within range: (1.05 to 1.2) x I1
S
± 10 %
I / 2I
± 15 %
G
± 15 %
UF / UF2 / OF /
± 2 %
OF2
Other
--
Trip threshold
Trip time tolerance
tolerance
(3)
t
± 10 %
with If ≤ 6 In: ± 7 % / with If > 6 In: ± 10 %
± 10 %
± 10 %
± 15 %
± 20 %
± 15 %
± 20 %
ABB | SACE Tmax XT
(example: If = 0.8 In, I1= 0.6 In)
t
Trip time tolerance
± 20 %
± 20 %
≤ 60 ms
± 20 % (60 ms with t4 = instantaneous)
± 20 %
± 20 %
Protections | 11 - Performance table