ABB SACE Tmax XT5 Operation And Maintenance Manual page 145

Tmax low voltage moulded-case circuit-breakers xt5
Hide thumbs Also See for SACE Tmax XT5:
Table of Contents

Advertisement

Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
143 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
communication:
Parameter
Description
Parameter for changing the configuration of the module from Server
Only to Client and Server and for integrating it into an interactive data
Client/Server
exchange network (see Ekip Com Hub on page 157)
IMPORTANT: if Client/Server, the module allows data
exchange like a normal Server function
IEEE 1588
Allows the IEEE 1588 protocol for distribution of the clock and
enable
synchronization signal to be enabled
Master IEEE
Enables the module to be set up as a master in the the network
1588
segment to which it belongs (synchronization clock).
IEEE 1588 delay
Allows the data exchange mode between module and master, either
mechanism
Peer-to-Peer or End-to-End, to be selected.
SNTP Client
Allows the SNTP protocol for distribution of the clock and
enable
synchronization signal to be enabled
Force Static IP
Allows the network server that supplies the SNTP to be set.
Address
Time zone
Defines the time zone to be used for synchronism
Daylight Saving
Used to select whether daylight saving time is present (ON) or not
Time
(OFF) in the country to which the synchronization time refers
Permits (Enabled ARP) the periodic generation of a Gratuituos ARP
Disabilita
message, used by Ekip Connect to rapidly find the modules via
Gratuitos ARP
Ethernet scan without knowing the IP address beforehand
Access
Enables the writing operations performed via the network to be
protected by
protected by a password (Request password)
password
Password
With access protected by enabled password, this is the password to
Modbus TCP
use before each writing session
(1)
Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
(2)
the parameter can only be changed via system bus in the remote configuration
communication:
Information
Description
Boot and HW version
General module information
Flash CRC status e result Information about the correctness of the SW in the module
Stato Ekip Link
Signals Ethernet cable connection errors
SNTP Server Error
Error in communication with SNTP server
SNTP Server
State of synchronism with SNTP server
Synchronisation
Valid with Master IEEE 1588= ON, notifies the presence (Slave or PTP Master
IEEE 1588 status
Active) or absence (PTP Master but Passive) of the higher level master
.
(1)
(1)
.
(2)
External accessories | 7 - Ekip Com Modbus TCP
ABB | SACE Tmax XT
Default
Server only
OFF
OFF
End-to-End
OFF
0.0.0.0
+00:00
OFF
ARP Enabled
Standard mode
Local access