Cable/Terminal Specifications

Installation should conform to NEC Article 110
the Occupational Safety and Health Administration, and any other applicable national, regional, or
industry codes and standards.
Note:
The following ratings are guidelines and shall not be the sole determining factor of the
lug or wire size used with the Q9 Plus ASD. Application-specific applicables, wire
insulation type, conductor material, and local and regional regulations are but a few of
the considerations when selecting the actual lug and wire type to be used with the Q9
Plus ASD.
Note:
Cable/Terminal specifications are based on the rated current of the Q9 Plus ASD and
Do Not include the 10% Service Factor.
Note:
Use only 75° C copper wire/cable for motor and power connections.
Table 25. 230-Volt Q9 Plus ASD Cable/Terminal/Torque Specifications.
Wire/Cable Size
Model
Number
VT130Q9+
Input/Output Power
Recommended
2015
14
2025
14
2035
14
2055
10
2080
8
2110
8
2160
6
2220
4
2270
3
2330
2
2400
1/0
266
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
(Requirements for Electrical Installations), all regulations of
Lug Size Range
AWG or kcmil
Wire-Size/Lug-Capacity for
Input/Output Power
Maximum
3Ø-Input
10
10
14 to 10
10
10
8
12 to 8
8
10 to 4
3
8 to 2
3
3
4 to 1/0
2
4/0
2 to 300
Terminal
Board Wire
Size
In-Lbs./N·m
TB1 – 4
3Ø-Output
Terminals
20
(3-core shield)
Torque to 5.3/0.6
Q9 Plus ASD Installation and Operation Manual
Torque
3Ø-Input 3Ø-Output
12.4/1.4
26.6/3
47.8/5.4
212/24
360/41