F849
Communication 2 Time-Out Condition
Program Communications Communication Options
This parameter determines the condition under which the drive will detect
time-out errors.
Settings:
0 — Always Detect
1 — Detect Time-Out Error During Communications
2 — Detect Time-Out Error During Communications and Running
Disconnection Detection Extended Time
Program Communications Communication Options
This parameter is used to set the length of time that no communications activity
may exist before the communications link is disconnected.
ASD Operation at Disconnect
Program Communications Communication Options
This parameter is used to set the Q9 Plus ASD action to be carried out in the
event of the loss of communications.
Settings:
0 — Stop and Terminate Communication
1 — Do Nothing (Continue Programmed Operation)
2 — Deceleration Stop
3 — Coast Stop
4 — Emergency Off
5 — Preset Speed (Setting of F852)
Preset Speed Operation
Program Communications Communication Options
This parameter setting is used to set the Preset Speed selection to be used if
Preset Speed is selected at parameter F851.
Settings:
0 — Disabled
1–15 — Preset Speed Number
Communications Option Station Address Monitor
Program Communications Communication Options
This parameter is used in the setup of the communications network by reading
the Media Access Code (MAC) address of the ASD that is connected to a node
of the communications system.
The MAC Address is set via DIP switches of the optional device.
See the DeviceNet Option Instruction Manual (P/N 58683) for additional
information on this parameter.
212
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Direct Access Number — F849
Parameter Type — Selection List
Factory Default — Always Detect
Changeable During Run — Yes
Direct Access Number — F850
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — Seconds
Direct Access Number — F851
Parameter Type — Selection List
Factory Default — Stop and Terminate
Communication
Changeable During Run — Yes
Direct Access Number — F852
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
Direct Access Number — F853
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
Minimum — 0
Maximum — 127
Q9 Plus ASD Installation and Operation Manual
F853