Analog Input Function Target 21
Program My Function My Function Analog
This parameter plays a role in the setup of the My Function feature by
selecting the functionality of the programmable Analog Input Function
Target 21 terminal.
The function selected at
F964
signal selected here.
Settings:
0 — Disabled (None)
1 — V/I
2 — RR
3 — RX
4 — Optional RX2+, RX2-
5 — Optional V/I
6 — Internal Memory
Analog Function Assigned Object 21
Program My Function My Function Analog
This parameter plays a role in the setup of the My Function feature by
selecting the functionality to which the adjustment of
Settings:
0 — Disabled (None)
1 — Acceleration Rate
2 — Upper-Limit Frequency
3 — Acceleration Multiplication Factor
4 — Deceleration Multiplication Factor
5 — Manual Torque Boost
6 — Over-Current Stall (F601)
7 — Thermal Protection
8 — Speed Loop Proportional Gain (F460)
9 — Drooping Gain (F320)
10 — PID Proportional Gain (F362)
See the My Function Instruction Manual (P/N E6581335) for a complete
description of the setup requirements and operational information of the
Analog Function Assigned Object parameter.
Monitor Output Function 11
Program My Function My Function Monitor
This parameter plays a role in the setup of the My Function feature by
establishing the function that is to be recorded and output as the Peak,
Minimum, or Average value as selected at parameter F966.
Select the Monitor Display Input Setting number from
output the corresponding function.
Use the Communication Number if operating using communications.
See the My Function Instruction Manual (P/N E6581335) for a complete
description of the setup requirements and operational information of the
Monitor Output Function parameter.
Q9 Plus ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
may be adjusted using the input analog control
F962
is applied.
Table 15 on pg. 242
Direct Access Number — F962
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
Direct Access Number — F964
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — No
Direct Access Number — F965
Parameter Type — Selection List
Factory Default — 2000
Changeable During Run — Yes
to
F965
227