F620
Cooling Fan Control
Program Protection Special Protection Parameters
This parameter sets the cooling fan run-time command.
Settings:
0 — Automatic
1 — Always On
Cumulative Operation Time Alarm Setting
Program Protection Special Protection Parameters
This parameter sets a run-time value that, once exceeded, closes a discrete
output contact. The output signal may be used to control external equipment or
used to engage a brake.
Associate the Total-Operation-Hours Alarm setting of
a discrete output contactor.
Note:
The time displayed is 1/10th of the actual time (0.1 hr. = 1.0 hr.).
Abnormal Speed Detection Time
Program Protection Abnormal Speed Settings
This parameter sets the time that an over-speed condition must exist to cause a
trip.
This parameter functions in conjunction with the settings of
Over-Speed Detection Frequency Upper Band
Program Protection Abnormal Speed Settings
This parameter sets the upper level of the Base Frequency range that, once
exceeded, will cause an Over-Speed Detected alert.
This parameter functions in conjunction with the settings of
Over-Speed Detection Frequency Lower Band
Program Protection Abnormal Speed Settings
This parameter sets the lower level of the Base Frequency range that, once the
output speed falls below this setting, will cause a Speed Drop Detected alert.
This parameter functions in conjunction with the settings of
Under-Voltage Detection Level
Program Protection Under-Voltage/Ridethrough
This parameter sets the voltage threshold level that is used as a setpoint for
under-voltage tripping.
This function is enabled at F627.
Q9 Plus ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Direct Access Number — F620
Parameter Type — Selection List
Factory Default — Automatic
Changeable During Run — Yes
Direct Access Number — F621
Parameter Type — Numerical
Factory Default — 610.0
Changeable During Run — Yes
Minimum — 0.0
Table 13 on pg. 239
to
Maximum — 999.9
Units — Hours (X 10)
Direct Access Number — F622
Parameter Type — Numerical
Factory Default — 0.01
Changeable During Run — Yes
Minimum — 0.01
F623
and F624.
Maximum — 100.00
Units — Seconds
Direct Access Number — F623
Parameter Type — Numerical
Factory Default — 0.00 (Disabled)
Changeable During Run — Yes
Minimum — 0.00 (Disabled)
F622
and F624.
Maximum — (ASD-Dependent)
Units — Hz
Direct Access Number — F624
Parameter Type — Numerical
Factory Default — 0.00 (Disabled)
Changeable During Run — Yes
Minimum — 0.00 (Disabled)
F622
and F623.
Maximum — (ASD-Dependent)
Units — Hz
Direct Access Number — F625
Parameter Type — Numerical
Factory Default — 60
Changeable During Run — No
Minimum — (ASD-Dependent)
Maximum — (ASD-Dependent)
Units — %
F625
179