Manual Torque Boost 1
Program Fundamental Motor Set 1
The Manual Torque Boost 1 function is used to increase the low frequency
torque for high-inertia loads by increasing the output voltage at frequencies
below ½ of the Base Frequency 1 (F014) setting.
The value programmed as a boost percentage establishes an output voltage vs.
output frequency relationship to be used to start the motor or to provide
smoother operation.
Note:
Setting an excessive Torque Boost level may cause nuisance
tripping and mechanical stress to loads.
Motor Overload Protection Configuration
Program Protection Overload
This parameter is used to enable the Soft Stall feature which protects the motor
from an over-current condition by reducing the output frequency during a
temporary increased current requirement from the load.
A V/f motor may be specified here along with the Overload Stall to better
match the ASD to the application.
This parameter setting may extend the Over-Voltage Stall time settings.
Settings:
0 — Motor Overload Trip without Soft Stall
1 — Motor Overload Trip with Soft Stall
2 — Without Motor Overload Trip or Soft Stall
3 — Soft Stall Only
4 — V/f Motor Overload Trip without Soft Stall
5 — V/f Motor Overload Trip with Soft Stall
6 — V/f Motor without Overload Trip or Soft Stall
7 — V/f Motor Soft Stall Only
88
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Direct Access Number — F016
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — 30.0
Units — %
Direct Access Number — F017
Parameter Type — Selection List
Factory Default — Motor Overload Trip
with Soft Stall
Changeable During Run — Yes