F442
Regenerative Braking Torque Limit 1
Program  Torque Torque Limit Settings
This parameter determines the source of the Regenerative Torque Limit
control signal.
If
F443
is selected, the value set at
Limit setting.
Settings:
1 — V/I
2 — RR
3 — RX
4 —
F443
(Setting)
Regenerative Braking Torque Limit 1 Level
Program Torque Torque Limit Settings
This parameter provides a value to be used as the Regeneration Torque
Limit 1 if
F443
is selected at parameter F442.
Set this parameter to 250% to disable this function.
Virtual Linear Pump Low Suction/No-Flow Cut Off Fault
Disposition
Program Virtual Linear Pump Low Suction/No-Flow Cut Off
This parameter is used in conjunction with the setting of parameter F483.
If On (Physical Switch) or On (Electronic Switch) is selected at parameter
F483, then this parameter selection sets the disposition of the system in the
event of a Low Suction/No-Flow Cut Off condition that exists for the duration
of the parameter
F484
setting.
If Off is selected at parameter F483, then this parameter selection is ignored.
Settings:
0 — Trip
1 — Alarm
2 — Alarm (auto-restart)
Constant Output Zone Torque Limit
Program Torque Torque Limit Settings
This parameter is used to select if either Constant Torque is applied to the load
as selected (selection 1) or if the ASD is allowed to use an over-voltage
condition to support a torque requirement at the load that exceeds that of the
Constant Torque operation setting during an active over-speed (selection 0).
Settings:
0 — Constant Output Limit
1 — Constant Torque Limit
Q9 Plus ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
F443
is used as the Regenerative Torque
Direct Access Number — F442
Parameter Type — Selection List
Factory Default —
F443
Setting
Changeable During Run — Yes
Direct Access Number — F443
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Direct Access Number — F450
Parameter Type — Selection List
Factory Default — Trip
Changeable During Run — Yes
Direct Access Number — F454
Parameter Type — Selection List
Factory Default — Constant Output
Limit
Changeable During Run — No
F454
159