Toshiba VLP Technology Q9 Plus Installation & Operation Manual page 116

Asd
Table of Contents

Advertisement

F198
V/f 5-Point Setting Frequency 5
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Frequency 5 sets the frequency to be associated with
the voltage setting of parameter
See
F190
and
F191
for additional information on this parameter.
V/f 5-Point Setting Voltage 5
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Voltage 5 establishes the output voltage level that is to
be associated with the frequency setting of
Frequency 5).
The
F701
parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See
F190
and
F191
for additional information on this parameter.
Frequency Priority Selection
Program Fundamental Standard Mode Selection
Either Frequency Mode 1 or Frequency Mode 2 may control the output
frequency of the ASD. This parameter determines which of the two will control
the output frequency and the conditions in which control will be switched from
one to the other.
Note:
Frequency Mode is abbreviated as FMOD.
The Frequency Mode 1 or Frequency Mode 2 selection specifies the source of
the input frequency command signal. These selections are performed at
and F207, respectively.
If FMOD changed by Terminal Board is selected here, the ASD will follow
the control of the discrete input terminal assigned the function of Frequency
Priority. The discrete terminal Frequency Priority will toggle control to and
from Frequency Mode 1 and Frequency Mode 2 with each activation/
deactivation.
If FMOD (F208) is selected here, the ASD will follow the control of the
Frequency Mode 1 setting for the duration that the commanded frequency of
the Frequency Mode 1 setting is greater than the setting of F208.
If the commanded frequency of the Frequency Mode 1 setting is less than or
equal to the setting of F208, the ASD will follow the setting of Frequency
Mode 2.
Settings:
0 — FMOD changed by Terminal Board (Frequency Mode)
1 — FMOD (F208) (Frequency Mode)
Q9 Plus ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
F199
(V/f 5-Point Setting Voltage 5).
(V/f 5-Point Setting 
F198
Direct Access Number — F198
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — Maximum Freq. (F011)
Units — Hz
Direct Access Number — F199
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — %
Direct Access Number — F200
Parameter Type — Selection List
Factory Default — FMOD
(changed by TB)
Changeable During Run — Yes
F004
F200
107

Advertisement

Table of Contents
loading

Table of Contents