Regenerative Power Ridethrough Mode
Program Protection Under-Voltage/Ridethrough
This parameter determines the motor control response of the ASD in the event
of a momentary power outage or under-voltage condition.
During a Ridethrough, regenerative energy is used to maintain the control
circuitry settings for the duration of the Ridethrough; it is not used to drive the
motor. The motor(s) of the system are stopped and then restarted automatically
if so configured.
Note:
If used to restart the motors, the Retry setup of
Settings:
0 — Off
1 — Ridethrough
2 — Deceleration Stop
Ridethrough Setup Requirements
1.
Select the Ridethrough Mode at F302.
2.
Select the Ridethrough Time at F310.
Q9 Plus ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Direct Access Number — F302
Parameter Type — Selection List
Factory Default — Off
Changeable During Run — No
F301
is required.