F125
Input Terminal 15 (LI7) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the LI7 discrete input terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable LI7 terminal to one of
the user-selectable functions listed in
Note:
The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.
See the Expansion IO Card Option 2 instruction manual (P/N 58686) for
additional information on the function of this terminal.
Input Terminal 16 (LI8) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the LI8 discrete input terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable LI8 terminal to one of
the user-selectable functions listed in
Note:
The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.
See the Expansion IO Card Option 2 instruction manual (P/N 58686) for
additional information on the function of this terminal.
Always ON Terminal Function 2
Program Terminal Input Terminals
This parameter is used to set the functionality of the virtual discrete input
terminal Always ON Terminal Function 2. As a virtual terminal, this control
terminal exists only in memory and is considered always to be in its True
(connected to CC) state.
It is often practical to assign a function to this terminal that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets the programmable ON terminal to one of the user-selectable
functions listed in
Table 10 on pg.
Always ON Terminal Function 3
Program Terminal Input Terminals
This parameter is used to set the functionality of the virtual discrete input
terminal Always ON Terminal Function 3. As a virtual terminal, this control
terminal exists only in memory and is considered always to be in its True
(connected to CC) state.
It is often practical to assign a function to this terminal that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets the programmable ON terminal to one of the user-selectable
functions listed in
Table 10 on pg.
98
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Table 10 on pg.
234.
Table 10 on pg.
234.
234.
234.
Direct Access Number — F125
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
Direct Access Number — F126
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
Direct Access Number — F127
Parameter Type — Selection List
Factory Default — (ASD-Dependent)
Changeable During Run — No
Direct Access Number — F128
Parameter Type — Selection List
Factory Default — (ASD-Dependent)
Changeable During Run — No
Q9 Plus ASD Installation and Operation Manual
F128