F652
Under-Torque Detection Level During Power Running
Program Protection Under-Torque Detection
While the motor is being driven by the ASD, this setting is used to set a low-
torque threshold minimum level that must exist for the duration of the parameter
F654
time setting to activate the Under-Torque disposition of the parameter
F651
setting.
Under-Torque Detection Level During Regenerative Braking
Program Protection Under-Torque Detection
During regeneration, this setting is used to set a low-torque threshold minimum
level that must exist for the duration of the parameter
activate the Under-Torque disposition of the parameter
Under-Torque Detection Time
Program Protection Under-Torque Detection
This parameter sets the time that the low-torque condition must exist to activate
the Under-Torque disposition of the parameter
Under-Torque Detection Hysteres
Program Protection Under-Torque Detection
With Alarm selected at parameter F651, this parameter setting is used to set the
hysteresis threshold of the low-torque condition for which the system must
return to deactivate the Under-Torque Alarm setting of parameter
return to normal system operation.
If Trip is selected at parameter F651, the same threshold applicables are in
effect with the addition that operator intervention will be required to return the
system to the normal operating condition. Remove the source of the trip
condition and/or perform a system reset.
Q9 Plus ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
F654
time setting to
F651
setting.
F651
setting.
F651
and to
Direct Access Number — F652
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Direct Access Number — F653
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Direct Access Number — F654
Parameter Type — Numerical
Factory Default — 0.50
Changeable During Run — Yes
Minimum — 0.00
Maximum — 10.00
Units — Seconds
Direct Access Number — F655
Parameter Type — Numerical
Factory Default — 10.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 100.00
Units — %
F655
185