Output Terminal 8 (OUT6) Function
Program Terminal Output Terminals
This parameter is used to set the functionality of the OUT6 discrete output
terminal.
In addition, this output terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable OUT6 terminal to one of
the user-selectable functions listed in
Note:
The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.
See the Expansion IO Card Option 2 instruction manual (P/N 58686) for
additional information on the function of this terminal.
Output Terminal 9 (R2) Function
Program Terminal Output Terminals
This parameter is used to set the functionality of the R2 discrete output
terminal.
In addition, this output terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable R2 terminal to one of the
user-selectable functions listed in
Note:
The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.
See the Expansion IO Card Option 2 instruction manual (P/N 58686) for
additional information on the function of this terminal.
Input Terminal 1 (F) Response Time
Program Terminal Input Terminal Delays
This parameter delays the response of the ASD to any change in the F terminal
input by the programmed value.
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Q9 Plus ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Table 13 on pg.
239.
Table 13 on pg.
239.
Direct Access Number — F137
Parameter Type — Selection List
Factory Default — Always Off
Changeable During Run — No
Direct Access Number — F138
Parameter Type — Selection List
Factory Default — Always Off
Changeable During Run — No
Direct Access Number — F140
Parameter Type — Numerical
Factory Default — 8
Changeable During Run — No
Minimum — 2
Maximum — 200
Units — mS
F140