Toshiba VLP Technology Q9 Plus Installation & Operation Manual page 196

Asd
Table of Contents

Advertisement

F670
AM Output Terminal Function
M
Program Terminal Analog Output Terminals
This parameter is used to set the output function of the AM analog output
terminal. The AM analog output terminal produces an output voltage that is
proportional to the magnitude of the function assigned to this terminal. The
available assignments for this output terminal are listed in
Note: To read current at this terminal, connect a 100 – 500 resistor from
the AM (+) terminal through the series Ammeter to the CC (-)
terminal.
AM Terminal Setup Parameters
F670
— Set AM Function
F671
— Calibrate AM Terminal
F685
— AM Output Gradient Characteristic
F686
— Set Zero Level
See
F678
for additional information on this parameter.
AM Output Terminal Adjustment
Program Terminal Analog Output Terminals
This parameter is used to calibrate the AM analog output.
To calibrate the AM analog output, connect an ammeter as described at
parameter F670.
While the ASD is running at a known value (e.g., output frequency), adjust this
parameter until the associated function of parameter
DC level output at the AM output terminal.
See
F670
for additional information on this parameter.
MON 1 Terminal Meter Selection
Program Terminal Analog Output Terminals
This parameter is used to set the output function of the MON1 analog output
terminal. The available assignments for this output terminal are listed in
11 on pg.
237.
The MON1 analog output terminal produces an output voltage or current that is
proportional to the magnitude of the function assigned to this terminal.
Note:
The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.
See the Expansion IO Card Option 2 instruction manual (P/N 58686) for
additional information on the function of this terminal.
MON1 Terminal Setup Parameters
F672
— MON1 Output Function
F673
— MON1 Terminal Meter Adjustment
F688
— MON1 Voltage/Current Output Switching
F689
— MON1 Output Gradient Characteristic
F690
— MON1 Bias Adjustment Set Zero Level
Q9 Plus ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Table 11 on pg.
237.
F670
produces the desired
Table
Direct Access Number — F670
Parameter Type — Selection List
Factory Default — Output Current
Changeable During Run — Yes
Direct Access Number — F671
Parameter Type — Numerical
Factory Default — 154
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
Direct Access Number — F672
Parameter Type — Selection List
Factory Default — Output Voltage
Changeable During Run — Yes
F672
187

Advertisement

Table of Contents
loading

Table of Contents