LED
LCD
Screen
Screen
Over-Current
OC1, OC1P
Acc
Over-Current
OC2, OC2P
Dec
Over-Current
OC3, OC3P
Run
Note:
The event that caused the trip(s) must be corrected or must decrease to less than the threshold value
required to cause the trip to allow for a Reset to be recognized. In the event of multiple active trips, the
trip displayed will remain until all faults are corrected and cleared.
254
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Table 19. Fault Codes (Continued)
Fault Description
Over-Current During
Acceleration.
Over-Current During
Deceleration.
Over-Current During Fixed
Speed Operation.
Possible Cause
• V/f setting needs to be adjusted.
• Restart from a momentary power outage.
• The ASD is starting into a rotating motor.
• ASD/Motor is improperly matched to the
application.
• Phase-to-phase short (U/T1, V/T2, or W/T3).
• Acceleration time is too short.
• Voltage Boost setting is too high.
• Motor/machine is jammed.
• Mechanical brake is engaged while the ASD is
running.
• ASD current exceeds 320% or 340% of the rated
FLA on ASDs that are greater than 100 HP or
that are 100 HP or less, respectively, during
acceleration.
• Phase-to phase short (U/T1, V/T2, or W/T3).
• Deceleration time is too short.
• Motor/machine is jammed.
• Mechanical brake is engaged while the ASD is
running.
• ASD current exceeds 320% or 340% of the rated
FLA on ASDs that are greater than 100 HP or
that are 100 HP or less, respectively, during
acceleration.
• ASD/Motor is improperly matched to the
application.
• Load fluctuations.
• ASD is operating at an elevated temperature.
• ASD current exceeds 320% or 340% of the rated
FLA on ASDs that are greater than 100 HP or
that are 100 HP or less, respectively, during
acceleration.
Q9 Plus ASD Installation and Operation Manual