F951
Input Function Target 3
Program My Function My Function Unit 6
This parameter plays a role in the setup of the My Function feature by
selecting the functionality of the programmable Input Function Target 3
terminal.
This setting assigns the function of the programmable Input Function Target 3
terminal to any one of the user-selectable functions listed in
238,
Table 13 on pg.
239, or
See
F977
for additional information on this parameter.
Output Function Assigned
Program My Function My Function Unit 6
This parameter plays a role in the setup of the My Function feature by
selecting the functionality of the Output Function Assigned terminal.
This setting assigns the function of the programmable Output Function
Assigned data location to one of the functions listed in the Input Setting field
of
Table 13 on pg.
239.
Settings:
0 – 3099
See the My Function Instruction Manual (P/N E6581335) and
additional information on this parameter.
Input Function Target 1
Program My Function My Function Unit 7
This parameter plays a role in the setup of the My Function feature by
selecting the functionality of the programmable Input Function Target 1
terminal.
This setting assigns the function of the programmable Input Function Target 1
terminal to any one of the user-selectable functions listed in
238,
Table 13 on pg.
239, or
See
F977
for additional information on this parameter.
Input Function Command 1
Program My Function My Function Unit 7
This parameter is used to assign a user-selected logical operator to two user-
selected Input Function Target variables, enable a counter/timer function, or
perform a hold/reset function.
Table 16 on pg. 244
lists the available selections. Their use and selection
requirements are described in an example at F977.
224
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Table 15 on pg.
242.
Table 15 on pg.
242.
Direct Access Number — F951
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
Table 12 on pg.
Direct Access Number — F952
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
F977
for
Direct Access Number — F953
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
Table 12 on pg.
Direct Access Number — F954
Parameter Type — Selection List
Factory Default — 0 (NOP)
Changeable During Run — Yes