F673
MON 1 Terminal Meter Adjustment
Program Terminal Analog Output Terminals
This parameter is used to set the gain of the MON1 output terminal and is used
in conjunction with the settings of parameter F672.
See
F672
for additional information on this parameter.
MON 2 Terminal Meter Selection
Program Terminal Analog Output Terminals
This parameter is used to set the output function of the MON2 analog output
terminal. The available assignments for this output terminal are listed in
11 on pg.
237.
The MON2 analog output terminal produces an output voltage or current that is
proportional to the magnitude of the function assigned to this terminal.
Note:
The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.
See the Expansion IO Card Option 2 instruction manual (P/N 58686) for
additional information on the function of this terminal.
MON2 Terminal Setup Parameters
F674
— MON2 Output Function
F675
— MON2 Terminal Meter Adjustment
F691
— MON2 Voltage/Current Output Switching
F692
— MON2 Output Gradient Characteristic
F693
— MON2 Bias Adjustment Set Zero Level
MON 2 Terminal Meter Adjustment
Program Terminal Analog Output Terminals
This parameter is used to set the gain of the MON2 output terminal and is used
in conjunction with the settings of parameter F674.
See
F674
for additional information on this parameter.
FP
Pulse Output Function
Program Terminal Analog Output Terminals
This parameter sets the functionality of the FP output terminal to any one of the
user-selectable functions listed in
As the assigned function changes in magnitude or frequency, the pulse count of
the FP output terminal pulse train changes in direct proportion to changes in the
assigned function.
Note:
The duty cycle of the output pulse train remains at 65 ±5.0 µS.
This parameter is used in conjunction with F677.
188
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Table 11 on pg.
237.
Direct Access Number — F673
Parameter Type — Numerical
Factory Default — 682
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
Direct Access Number — F674
Parameter Type — Selection List
Factory Default — Output Frequency
Changeable During Run — Yes
Table
Direct Access Number — F675
Parameter Type — Numerical
Factory Default — 682
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
Direct Access Number — F676
Parameter Type — Selection List
Factory Default — Output Frequency
Changeable During Run — Yes
Q9 Plus ASD Installation and Operation Manual