F223
RX2 Input Point 1 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX2 input terminal when
the RX2 terminal is used as the control input while operating in the Speed
Control mode.
This parameter sets RX2 Input Point 1 Frequency and is the frequency that is
associated with the setting of RX2 Input Point 1 Setting when operating in the
Speed Control mode.
See RX2 Input Point 1 Setting (F222) for additional information on this
parameter.
RX2 Input Point 2 Setting
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX2 input terminal when
the RX2 terminal is used as the control input while operating in the Speed
Control mode or the Torque Control mode.
This parameter sets the RX2 input level that is associated with RX2 Input
Point 2 Frequency when operating in the Speed control mode or is associated
with the RX2 Input Point 2 Rate when operating in the Torque Control
mode.
This value is entered as -100% to +100% of the RX2 input signal range.
See RX2 Input Point 1 Setting (F222) for additional information on this
parameter when used for Speed control.
RX2 Input Point 2 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX2 input terminal when
the RX2 terminal is used as the control input while operating in the Speed
Control mode.
This parameter sets RX2 Input Point 2 Frequency and is the frequency that is
associated with the setting of RX2 Input Point 2 Setting when operating in the
Speed Control mode.
See RX2 Input Point 1 Setting (F222) for additional information on this
parameter.
120
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Direct Access Number — F223
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Maximum Freq. (F011)
Units — Hz
Direct Access Number — F224
Parameter Type — Numerical
Factory Default — +100
Changeable During Run — Yes
Minimum — -100
Maximum — +100
Units — %
Direct Access Number — F225
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.00
Maximum — Maximum Freq. (F011)
Units — Hz
Q9 Plus ASD Installation and Operation Manual
F225