F206
V/I Input Point 2 Rate
Program Torque Setpoints
This parameter is used to set the gain and bias of the V/I input terminal when
the V/I terminal is used as the control input while operating in the Torque
Control mode.
Torque Control is accomplished by establishing an associated V/f output pattern
for a given V/I input level.
This parameter sets V/I Input Point 2 Rate and is the output torque value that
is associated with the setting of V/I Input Point 2 Setting when operating in
the Torque Control mode.
This value is entered as 0% to 250% of the rated torque.
See V/I Input Point 1 Rate (F205) for additional information on this
parameter.
Frequency Mode 2
Program Fundamental Standard Mode Selection
This parameter is used to set the source of the frequency command signal to be
used as Frequency Mode 2 in the event that Frequency Mode 1 is disabled or
if Frequency Mode 2 is set up as the primary control parameter.
See
F004
and
F200
for additional information on this parameter.
Settings:
1 — V/I
2 — RR
3 — RX
4 — Panel Keypad
5 — RS485 2-Wire (EOI)
6 — RS485 4-Wire (Terminal Board)
7 — Communication Option Board
8 — RX2
9 — Option V/I
10 — UP/DOWN Frequency
11 — Optional RP Pulse Input
12 — Optional High-Speed Pulse Input
Frequency Mode Priority Switching Frequency
Program Fundamental Standard Mode Selection
This parameter establishes a threshold frequency that will be used as a reference
when determining when to switch the output frequency control source from the
Frequency Mode 1 setting to the Frequency Mode 2 setting.
See
F200
for additional information on this parameter.
Q9 Plus ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Direct Access Number — F206
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Direct Access Number — F207
Parameter Type — Selection List
Factory Default — V/I
Changeable During Run — No
Direct Access Number — F208
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — (ASD-Dependent)
Maximum — Maximum Freq. (F011)
Units — Hz
F208