F822
Baud Rate Monitor Right Port (Ethernet)
Program Communications Ethernet Settings
This parameter establishes the baud rate detection setting of the right port.
Settings:
0 — Automatic Detection
1 — 10Mbps Full
2 — 10Mbps Half
3 — 100Mbps Full
4 — 100Mbps Half
Baud Rate Monitor Left Port (Ethernet)
Program Communications Ethernet Settings
This parameter establishes the baud rate detection setting of the left port.
Settings:
0 — Automatic Detection
1 — 10Mbps Full
2 — 10Mbps Half
3 — 100Mbps Full
4 — 100Mbps Half
RS485 Send Delay Time (4-Wire RS485)
Program Communications Communication Settings
This parameter sets the RS485 response delay time.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Q9 Plus ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Direct Access Number — F822
Parameter Type — Selection List
Factory Default —Automatic Detection
Changeable During Run — Yes
Direct Access Number — F823
Parameter Type — Selection List
Factory Default —Automatic Detection
Changeable During Run — Yes
Direct Access Number — F825
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.00
Units — Seconds
F825