Control
Command control includes instructions such as Stop, Run, Jog, etc. The source of the Command
signal must be established for normal operation.
Frequency commands control the output speed of the Q9 Plus ASD. The source of the frequency
(speed) control signal must be established for normal operation.
The source of the command control and speed control may be either internal or external. Once the signal
source is selected for either function, the system may be configured to use the selected signal all of the
time or switch under user-defined conditions.
Command and Frequency control may be carried out using any one of several control methods (signal
sources) or combinations thereof. In the event that multiple control commands are received, the signal
sources are assigned priority levels. The primary control method for Command and Frequency control
uses the settings of
Command Control (F003)
The Command Mode selection of
ASD. However, the Override feature may supersede the
Table 3
shows the hierarchy of the control sources managed by the Override function. The level of the
control item on the hierarchy is listed from left to right, most to least, respectively. As indicated in the
table, the Override setting may supersede the
Placing the EOI in the Hand mode selects the RS485 (2-Wire) as the Command Mode control source.
Hand mode operation may be superseded by other Override settings.
Example: With the EOI set to Hand, Communication Card input or RS485 (4-Wire) input will
supersede EOI control input.
The remaining control sources may be placed into the Override Mode using communications.
The source of the Command control signal may be selected by:
• The
F003
setting,
• Placing an item from the list below in the Override Mode via communications, or
• Placing the EOI in the Hand mode (places only the RS485 [2-Wire] in the Override Mode).
Possible Command signal source selections include the following:
• Terminal Block (default setting),
• Panel Keypad Option,
• RS485 (2-Wire),
• RS485 (4-Wire),
• Communication Option Board, or
F003
setting (used if no signal sources are in the override mode).
Note:
The Terminal Board is placed in the Override Mode for Command functions by
assigning a discrete terminal to Command Terminal Board Priority and connecting
the terminal to CC. Once activated (run command required), the Terminal Board
settings will be used for Override Command control (F, R, Preset Speeds, etc.).
36
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
F003
and F004, respectively.
F003
establishes the primary source of the command input for the
F003
F003
setting as indicated in
setting.