F371
PID Output Lower Limit
Program Feedback Feedback Settings
Selecting Speed PID at parameter
function as the Lower Limit while operating in the PID Control mode.
Process Increasing Rate
Program Feedback Feedback Settings
This parameter is used to limit the rate that the output of the ASD may increase
for a given difference in the speed reference and the PID feedback value.
Process Decreasing Rate
Program Feedback Feedback Settings
This parameter is used to limit the rate that the output of the ASD may decrease
for a given difference in the speed reference and the PID feedback value.
Frequency Command Detection Range
Program Feedback Feedback Settings
While operating in the PID mode, this parameter reads the feedback frequency.
Once the feedback frequency is within the setting of this parameter (F374)
relative to the commanded frequency, a properly configured output terminal is
activated.
Available output terminal settings for this parameter include: FC = RR, FC =
RX, and FC = VI (see
Table 13 on pg.
command and RR, RX, and VI are the input terminals of the received feedback.
Number of PG Input Pulses
Program Feedback PG Settings
This parameter is used to set the number of pulses output from a shaft-mounted
encoder that is used to indicate one revolution of rotation (360°) of the motor or
of the motor-driven equipment.
146
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
F359
allows for this parameter setting to
239), where FC is the frequency
Direct Access Number — F371
Parameter Type — Numerical
Factory Default — Lower-Limit Freq.
(F013)
Changeable During Run — Yes
Minimum — Lower-Limit Freq. (F013)
Maximum — Upper-Limit Freq. (F012)
Units — Hz
Direct Access Number — F372
Parameter Type — Numerical
Factory Default — 10.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 600.0
Units — Seconds
Direct Access Number — F373
Parameter Type — Numerical
Factory Default — 10.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 600.0
Units — Seconds
Direct Access Number — F374
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.00
Maximum — Maximum Freq. (F011)
Units — Hz
Direct Access Number — F375
Parameter Type — Numerical
Factory Default — 500
Changeable During Run — No
Minimum — 1
Maximum — 9999
Q9 Plus ASD Installation and Operation Manual
F375