Toshiba VLP Technology Q9 Plus Installation & Operation Manual page 161

Asd
Table of Contents

Advertisement

F397
Virtual Linear Pump Command Value
Program Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation while operating
in the Process Hold mode and using the EOI for system control, this parameter
establishes the Virtual Linear Pump level.
This parameter setting is effective ONLY while operating in the Process Hold
mode and while receiving a command via the EOI. The end value of this
parameter setting appears in the Frequency Command screen as shown below.
Virtual Linear Pump Low Frequency Limit
Program Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this parameter
establishes the Virtual Linear Pump Low Frequency Limit.
Autotune 1
Program Motor Vector Motor Model
This parameter sets the Autotune command status.
Selecting Reset Motor Defaults for this parameter sets parameters F410, F411,
F412, and
F413
to the factory default settings.
If selecting Autotune on Run Command, Autotune Initiated by Input
Terminal, or Autotune of Detail Parameters for this parameter set the Base
Frequency, Base Frequency Voltage, and the Motor Rated Revolutions to
the nameplated values of the motor to achieve the best possible Autotune
precision.
Settings:
0 — Autotune Disabled
1 — Reset Motor Defaults
2 — Enable Autotune on Run Command
3 — Autotuning by Input Terminal Signal (see
4 — Motor Constant Auto Calculation
152
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Table 10 on pg.
234)
Q9 Plus ASD Installation and Operation Manual
Direct Access Number — F397
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum —
F403
Setting
Maximum —
F393
Setting
Direct Access Number — F398
Parameter Type — Numerical
Factory Default — 15.00
Changeable During Run — Yes
Minimum — 1.00
Maximum — 60.00
Units — Hz
Direct Access Number — F400
Parameter Type — Selection List
Factory Default — Autotune Disabled
Changeable During Run — No
F400

Advertisement