BACnet
Setup
®
The Q9 Plus ASD is a BACnet
support interoperable HVAC systems. This section provides useful setup and operational information for
using the BACnet
Perform the following parameter changes to allow the Q9 Plus ASD to communicate with the BACnet
network:
1. Set parameter
configured.
2. Set parameter
3. Set parameter
4. Set parameter
The Q9 Plus ASD is now configured to communicate with the BACnet
S4 Pinout
The
S4
RJ-45 connector is located on the Terminal Board and is used for serial communications
connectivity.
In order to use the S4 connector for serial communications, both
ON (2-wire configuration).
Shown below is the S4 connector pinout.
76
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
®
-compatible device. The BACnet
®
protocol with the Q9 Plus ASD to monitor and control HVAC systems.
F802
to select a unique number (Station ID) within the network for the ASD being
F827
to 0: No Parity.
F829
to 2: BACnet.
F899
to Reset Option Board and ASD.
Pin Number
1
2
3
4
5
6
7
8
®
communications protocol is used to
®
network.
SW200
switches (1 and 2) must be
S4 (RJ-45) Pinout
Do not connect
GND
Do not connect
Signal RS485-A
Signal RS485-B
Do not connect
Do not connect
GND
Q9 Plus ASD Installation and Operation Manual
®