Toshiba VLP Technology Q9 Plus Installation & Operation Manual page 152

Asd
Table of Contents

Advertisement

F355
Commercial Power/ASD Switching Frequency
Program Terminal Line Power Switching
When enabled at
F354
and with a properly configured discrete output terminal,
this parameter sets the frequency at which the At Frequency Powerline
Switching function engages.
The At Frequency Powerline Switching function commands the system to
discontinue using the output of the ASD and to switch to commercial power
once reaching the frequency set here.
See
F354
for additional information on this parameter.
ASD Side-Switching Delay Time
Program Terminal Line Power Switching
This parameter determines the amount of time that the ASD will wait before
outputting a signal to the motor once the switch-to-ASD-output criteria has
been met.
See
F354
for additional information on this parameter.
Commercial Power Side Switching Delay Time
Program Terminal Line Power Switching
This parameter determines the amount of time that the ASD will wait before
allowing commercial power to be applied to the motor once the switch-to-
commercial-power criteria has been met.
See
F354
for additional information on this parameter.
Commercial Power Switching Freq. Hold Time
Program Terminal Line Power Switching
This parameter determines the amount of time that the connection to
commercial power is maintained once the switch-to-ASD-output criteria has
been met.
See
F354
for additional information on this parameter.
PID Control Switching
Program Feedback Feedback Settings
This parameter is used to set the PID control mode.
Selecting Process PID uses the upper and lower-limit settings of parameters
F367
and F368.
Selecting Speed PID uses the upper and lower-limit settings of parameters
F370
and F371.
Settings:
0 — PID Off
1 — Process PID
2 — Speed PID
4 — Dancer Control
Q9 Plus ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Direct Access Number — F355
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.00
Maximum — Upper-Limit Freq. (F012)
Units — Hz
Direct Access Number — F356
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.10
Maximum — 10.00
Units — Seconds
Direct Access Number — F357
Parameter Type — Numerical
Factory Default — 0.62
Changeable During Run — Yes
Minimum — 0.40
Maximum — 10.00
Units — Seconds
Direct Access Number — F358
Parameter Type — Numerical
Factory Default — 2.00
Changeable During Run — Yes
Minimum — 0.10
Maximum — 10.00
Units — Seconds
Direct Access Number — F359
Parameter Type — Selection List
Factory Default — PID Off
Changeable During Run — No
F359
143