F401
Slip Frequency Gain
Program Motor  Vector Motor Model
This parameter provides a degree of slip compensation for a given load. A
higher setting here decreases the slip allowed for a given load/ASD output ratio.
Autotune 2
Program Motor Vector Motor Model
This parameter introduces a thermal element into the autotuning equation and is
used to automatically adjust the Autotune parameter values as a function of
increases in the temperature of the motor.
Settings:
0 — Off
1 — Self-Cooled Motor Tuning
2 — Forced Air Cooled Motor Tuning
(Virtual Linear Pump) Transducer Minimum Reading
Program Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this parameter
establishes the minimum level of the transducer range for Virtual Linear
Pump operation.
Q9 Plus ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Direct Access Number — F401
Parameter Type — Numerical
Factory Default — 70
Changeable During Run — Yes
Minimum — 0
Maximum — 150
Units — %
Direct Access Number — F402
Parameter Type — Selection List
Factory Default — Off
Changeable During Run — No
Direct Access Number — F403
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -3276.7
Maximum — 3276.7
F403
153