Toshiba VLP Technology Q9 Plus Installation & Operation Manual page 218

Asd
Table of Contents

Advertisement

F827
Parity (4-Wire RS485)
Program Communications Communication Settings
This parameter plays a role in the setup of the communications network by
establishing the Parity setting of the RS485 4-Wire communications
link.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
0 — No Parity
1 — Even Parity
2 — Odd Parity
Communications Protocol (4-Wire RS485)
Program Communications Communication Settings
This parameter sets the communications protocol for ASD-to-ASD
communications.
Settings:
0 — Toshiba
1 — Modbus
2 — BACnet
Communication Option (DeviceNet/Profibus) Setting 1
Program Communications Communication Options
While using the DeviceNet/Profibus communications protocol, this parameter
allows the user to select the read and write information communicated between
the ASD and the Host.
Read information may include the ASD fault status, ASD speed, ASD MAC
ID, etc. Write information may include Enable/Disable DeviceNet commands,
Forward run, ACC/DEC command, etc.
See the DeviceNet Option Instruction Manual (P/N 58683) for additional
information on this parameter.
Settings:
0 – 7
Q9 Plus ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Direct Access Number — F827
Parameter Type — Selection List
Factory Default — Even Parity
Changeable During Run — Yes
Direct Access Number — F829
Parameter Type — Selection List
Factory Default — Toshiba
Changeable During Run — Yes
Direct Access Number — F830
Parameter Type — Selection List
Factory Default — 0
Changeable During Run — Yes
F830
209

Advertisement

Table of Contents
loading

Table of Contents