F040
Automatic Function Selection
Program Utilities Display Parameters
This parameter setting is used to configure multiple parameters with the setting
of only one parameter. From the selection below, multiple parameters may be
set as indicated in the table.
Once set, the selected configuration is placed in effect and remains in effect
until this parameter is changed or the individual settings are changed.
Set this parameter to Disable to set these parameters individually.
Note:
After performing the desired selection, the EOI display returns to
Disabled though the selected function has been carried out (i.e.,
without this, if selection 1 is performed,
hold the RR terminal setting regardless of attempts to change the
settings individually).
Settings:
0 — Disabled
1 — RR
2 — V/I
3 — Select RR or V/I by TB (Terminal Board)
4 — Keypad Frequency and Command from TB (Terminal Board)
5 — Keypad Frequency and Command
6 — Coast Stop
0
Related
Default
Disabled RR
Params
Settings
Command
Terminal
Mode
Board
F003
Frequency
Mode 1
RR
N/C
F004
S3
Preset
Terminal
Speed 3
F117
Frequency
Terminal
Priority
N/C
Board
F200
V/I Setup
0.0%
N/C
F201
Frequency
Mode 2
V/I
N/C
F207
Always On
Not
F110
Assigned
N/C = No Change — the setting remains as it was before setting parameter F040.
Q9 Plus ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
F004
and
F207
User Selections
1
2
3
4
RR or
Keypad/
V/I
V/I via
Freq.
TB
CMD/TB
Terminal
N/C
Board
RR
N/C
RR
Keypad
Freq.
N/C
Ref.
N/C
Priority
Terminal Board
20.0%
N/C
RR
V/I
Keypad
N/C
Direct Access Number — F040
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
would
5
6
Keypad
Coast
Freq/CMD
Stop
Keypad
N/C
ST
N/C
N/C
N/C
0
F040
91