Cable/Terminal Specifications

Installation should conform to the 2005 National Electrical Code Article 110 (NEC) (Requirements for
Electrical Installations), all regulations of the Occupational Safety and Health Administration, and any
other applicable national, regional, or industry codes and standards.
Note:
The following ratings are guidelines and shall not be the sole determining factor of the
lug or wire size used with the ASD. Application-specific applicables, wire insulation type,
conductor material, and local and regional regulations are but a few of the
considerations when selecting the actual lug and wire type to be used with the ASD.
Note:
Cable/Terminal specifications are based on the rated current of the ASD and Do Not
include the 10% Service Factor.
For further installation information see the section titled
MCP
Model
Rating
VT130G7U
(Amps)
Recommended
2010B
15
2015B
15
2025B
15
2035B
20
2055B
30
2080B
50
2110B
50
2160B
75
2220B
100
2270B
125
2330B
150
2400B
175
2500B
200
2600B
250
2750B
300
210KB
400
212KB
500
215KB
600
Note:
Input and Output power wires require shielding for CE compliance.
Note:
(*) Indicates that the item is one of a set of two parallel cables.
G7 ASD Quick Start Guide
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Table 6. 230-volt G7 ASD Cable/Terminal Specifications.
Typical Wire/Cable Size (AWG or kcmil)
Input/Output Power
AM, FM, and II
Maximum
14
10
14
10
14
10
14
10
12
10
10
10
8
4
6
4
4
4
(3-core shield)
3
2
2
2
1/0
2/0
2/0
2/0
*1/0
*4/0
*2/0
*4/0
*4/0
*500
*300
*500
*400
*500
Installation and Connections on pg.
Control Terminals
Terminals
20
18
(2-core shield)
12.
Lug Size Range
Wire-Size/Lug-Capacity for
Input/Output Power
24 to 8
18 to 4
16 to 1
10 to 1/0
12 to 4/0
*(6 to 250)
*(1/0 to 500)