- Type 1
During installation, all conduit hole plugs shall be removed, and all conduit holes shall be used.
VDI100
1007
1015
2022
2037
2055
3075
4110
4150
4185
5220
356
Closed-Loop Crimp Terminal Size
Wire gauge (AWG)
R/L1 S/L2 T/L3
U/T1, V/T2,W/T3
2.5 (14)
4.0 (12)
6.0 (10)
6.0 (10)
10.0 (8)
25 (4)
55 (1/0)
2.5 (14)
4.0 (12)
6.0 (10)
4.0 (12)
6.0 (10)
10.0 (8)
16 (6)
35 (2)
95 (3/0)
120 (4/0)*2
Manufacturer: Bussmann/ FERRAZ SHAWMUT
Model
200V class three-phase drives
Bussmann 20CT
Bussmann 30FE
Bussmann 50FE
Bussmann 50FE
Bussmann 63FE
FERRAZ SHAWMUT A50QS100-4
Bussmann 120FEE / FERRAZ A50QS150-4
FERRAZ SHAWMUT A50QS150-4
FERRAZ SHAWMUT A50QS200-4
FERRAZ SHAWMUT A50QS250-4
Terminal
Crimp Terminal
Screws
Model No.
230V class three-phase drives
R2-4
M4
R5.5-4
M4
R5.5-4
M4
R8-4
M6
R22-6
M8
R60-8
400V class three-phase drives
R2-4
M4
R5.5-4
M4
R5.5-4
M4
R8-4
M6
R14-6
M8
R38-8
M10
R80-10
M10
R100-10
Fuse Type
Fuse ampere rating(A)
500 V / 100 A
690 V / 120 A - 500 V / 150 A
500 V / 150 A
500 V / 200 A
500 V / 250 A
Tool
Machine No.
Nichifu NH 1/9
Nichifu NH 1/9
Nichifu NOP 60
Nichifu NOP 60/150H
Nichifu NOP 60/150H
Nichifu NH 1/9
Nichifu NH 1/9
Nichifu NOP 60
Nichifu NOP 60/150H
Nichifu NOP 60/150H
Nichifu NOP 150H
Nichifu NOP 150H
690 V / 20 A
690 V / 30 A
690 V / 50 A
690 V / 50 A
690 V / 63 A
VDI100 • Instruction manual
Insulation Cap
Model No.
TIC 2
TIC 3.5
TIC 5.5
TIC 5.5
TIC 8
TIC 22
TIC 60
TIC 2
TIC 3.5
TIC 5.5
TIC 3.5
TIC 5.5
TIC 8
TIC 14
TIC 38
TIC 80
TIC 100