x0xxb: PID error value of D control
x1xxb: PID feedback value of D control
0xxxb: PID output
1xxxb: PID output + frequency command
PID control can be enabled by setting parameter 10-03 to 'xxx1b'
Commonly used PID control modes
0001b: Forward operation: PID operation enabled, motor speeds increases when feedback signal is smaller
than set-point (most fan and pump applications)
0011b: Reverse operation: PID operation enabled, motor slows down when feedback signal is smaller than set-
point (e.g. level control applications)
To set parameter 10-03:
-
After power-up press the DSP/FUN key
Set Group 10 (PID Control), and select parameter -03 with the UP/DOWN ▲ and ▼ keys and press the
-
READ/ ENTER key.
To use the PID function parameter 00-05 (Main Frequency Command Source Selection) has to be set to 5 for PID
reference.
Important
Pour pouvoir utiliser la fonction PID, le paramètre 00-05 (Sélection Source de Commande Fréquence Princi-
pale) doit être réglé sur 5 pour la référence PID.