■ Speed search based on current detection
(a) Speed search at starting
(b) Speed search in recovery period of momentary power failure
Notes:
If the minimum base block time (07-18) is longer than the momentary power failure time, the speed search starts
operation after the minimum base block time (07-18).
If the minimum base block time (07-18) is too short, the speed search operation begins immediately after power has
been restored.
Code
Parameter Name / Range
07-29
Run Command Selection at the Action of DC Braking
(0) Not Allowable to Run
(1) Allowable to Run
When DC braking is active, then:
07-29=0:
Inverter does not run again until DC braking stops.
07-29=1:
Inverter can run again even if DC braking is in action.
200
Figure 4.4.65 Speed search at starting
Run command
Search command
Output frequency
(07-18)
Output voltage
Output current
Figure 4.4.66 Speed search in recovery period of momentary power failure
Momentary power loss
Minimum b.b. time (07-18)
Run command
Search command
Output frequency
Output voltage
Output current
Speed search decel time (07-21)
V/f during speed search
Return to voltage at normal operation
Speed search
operation
(07-18)
Speed search decel time (07-21)
V/f during speed search
Speed search
operation
t
t
t
Voltage recovery time (07-23)
t
(07-20)
t
t
t
t
t
t
Return to voltage at normal operation
Voltage recovery time (07-23)
t
(07-20)
t