Se08 - gefran VDI100 Series Instruction Manual

General purpose full vector inverter
Hide thumbs Also See for VDI100 Series:
Table of Contents

Advertisement

LED display

SE08

PM Motor mode error
Inverter rating does not support
the PM Motor mode.
SE09
PI setting error
Inverter PI setting error
FB
(flash)
PID feedback signal falls below
PID feedback
level specified in 10-12 (PID feed-
braking
back loss detection level) for the
time specified in 10-13 (Feedback
loss detection time). Active when
parameter (10-11 = 1).
USP
(flash)
Unattended Start
Protection
Unattended Start Protection (USP)
is enabled (enabled at power-up.)
Zero Speed Stop Error
Frequency command is smaller
than 01-08 without DC brake.
External Terminal
External Terminal is main run
Stop Error
command source selection
(00-02=1) and run command
executes but executes stop
command from keypad.
Encoder Error
PG card is connected but encoder
signal error is detected when
motor auto rotational tuning is
running.
Wrong running direc-
tion Error
Running direction is different from
11-00
Parameter Lock
Parameter lock key code (pass-
word) already locked
Set password failed
Parameter lock key code cannot
enable
338
Description
• Inverter rating does not support PM motor
control mode.
• Inverter pulse input selection (03-30)
selection conflicts with PID source (10-00 and
10-01).
• Feedback signal wire broken
• Feedback sensor broken
• USP at power-up (activated by multi-function
digital input) is enabled. The inverter will not
accept a run command.
• While the warning is active the inverter does
not accept a run command. (See parameter
03-00 - 03-08 = 50).
• Frequency command is smaller than motor
minimum output frequency.
• Run command executes from external termi-
nal but executes stop command from keypad.
• Abnormal encoder signal
• Check the command among 11-00, jog and DI
control to see if any difference.
• Parameter lock key code already enable
(13-07)
• To enable the parameter lock key code (pass-
word) function, but the password is not correct
Possible causes
Corrective action
• Check control mode.
• Check pulse input selection (03-30) and PID
source (10-00 and 10-01).
• Check feedback wiring
• Replace feedback sensor.
• Remove run command or reset inverter via
multi-function digital input (03-00 to 03-07 =
17) or use the RESET key on the keypad to reset
inverter.
• Activate USP input and re-apply the power.
• Adjust frequency command
• Remove the run command from external
terminal
• Check encoder wiring
• 17-07 PG pulse number setting is not corre-
sponding to the encoder.
• Replace the encoder.
• Revise the command among 11-00, jog and
DI control to see if any difference
• Lifting the parameter lock key code, to enter
the correct parameter for 13-07
• Enter the correct parameter for 13-07 to
enable the parameter lock key
VDI100 • Instruction manual