gefran VDI100 Series Instruction Manual page 178

General purpose full vector inverter
Hide thumbs Also See for VDI100 Series:
Table of Contents

Advertisement

04-05=8: Frequency lower limit
Multi-function analog input AI2 can be used to adjust the lower limit of frequency reference.
Maximum output frequency (Fmax, 01-02) = 100%. The actual lower limit is determined by the maximum value
of 00-13 (frequency lower limit) and level of the multi-function analog input AI2.
04-05=9: Jump frequency 4
Multi-function analog input AI2 can be used to adjust Jump frequency 4.
Maximum output frequency (01-02, Fmax) = 100%. Setting 11-08 to 11-10 to 0.0Hz turns of the Jump frequen-
cy function.
04-05=10: Added to AI1
Multi-function analog input AI2 can be used as a bias level for analog input AI1.
178
Figure 4.4.47 Adjustment of lower limit of frequency reference
Frequency
Reference
Lower Bound
100
-10V
Figure 4.4.48 Jump frequency 4 Setting Operation
Jump
Frequency 4
100%
-
10V
0V
10V
(20mA)
(4mA)
(a) Jump Frequency 4 Adjustment
Figure 4.4.49 Operation of being added to Al1 as bias
Frequency
Reference
Bias
100%
-10V
%
10V
0V
(20mA)
(4mA)
Output
Frequency
Terminal AI2
analog input
Jump
Jump
Freq 3
Freq 4
(11-10)
Using
analog
input
(b) Jump Frequency Hierarchy
10V
0V
(20mA)
(4mA)
-
100%
Terminal AI2
analog input
Jump
Frequency
Jump
Jump
Reference
Freq 2
Freq 1
(11-09)
(11-08)
Terminal AI2
analog input
VDI100 • Instruction manual