gefran VDI100 Series Instruction Manual page 300

General purpose full vector inverter
Hide thumbs Also See for VDI100 Series:
Table of Contents

Advertisement

RTU Mode
Command Message
Node Address
Function
High
Test Code
Low
High
DATA
Low
High
CRC-16
Low
Write Single Holding Register [06H]
Write single holding register. The register address of the holding register is specified in the message.
Example: Write a 60.00Hz frequency command to node address 1.
ASCII Mode
Command Message
3AH
30H
31H
30H
36H
32H
35H
Starting Register
30H
32H
31H
37H
37H
30H
34H
42H
0DH
0AH
RTU Mode
Command Message
Node Address
Function
High
Start No
Low
High
DATA
Low
High
CRC-16
Low
Write Multiple Holding Register [10H]
Write multiple holding registers. The address of the first holding register is specified in the message.
Example: Write a 60.00Hz frequency command to node address 1 and enable FWD run command.
300
01 H
08H
00H
Test Code
00H
A5H
37H
DAH
CRC-16
8DH
STX
Node Address
Function
DATA
LRC CHECK
END
01 H
08H
25H
Start No
02H
17H
70H
2DH
CRC-16
12H
Response Message (Normal)
Node Address
01H
Function
08H
High
00H
Low
00H
High
A5H
DATA
Low
37H
High
DAH
Low
8DH
Response Message (Normal)
3AH
STX
30H
Node Address
31H
30H
Function
36H
32H
35H
Starting Register
30H
32H
31H
37H
DATA
37H
30H
34H
LRC CHECK
42H
0DH
END
0AH
Response Message (Normal)
Node Address
01H
Function
06H
High
25H
Low
02H
High
17H
DATA
Low
70H
High
2DH
Low
12H
Response Message (Error)
Node Address
01H
Function
88H
Exception code
03H
High
06H
CRC-16
Low
01H
Response Message (Error)
3AH
STX
30H
Node Address
31H
38H
Function
36H
30H
Exception code
33H
30H
LRC CHECK
32H
0DH
END
0AH
Response Message (Error)
Node Address
01H
Function
86H
Exception code
03H
High
02H
CRC-16
Low
61H