gefran VDI100 Series Instruction Manual page 318

General purpose full vector inverter
Hide thumbs Also See for VDI100 Series:
Table of Contents

Advertisement

Run/Stop from Serial Communication RS485 (00-02=3)
7.3.
CN6
8 7 6 5 4 3 2 1
Control board
S-
S+
Cable
Shield
RS485 Port
-
RS485 PLC / Computer Connection
+
To control (Run/Stop) the inverter via serial communication parameter 00-02 has be set to either a "3" for com-
munication control.
Default Communication Setting is: Address "1", 9600 Bits/sec, 1 Start Bit, 1 Stop Bit, and No Parity
The serial communication link function uses RS485 Modbus RTU protocol and allows for:
1) Monitoring (data monitoring, function data check).
2) Frequency setting.
3) Operation command (FWD, REV, and other commands for digital input).
4) Write function data.
Command Register
Inverter Command Register: 2501 (Hexadecimal)
Bit 0: Run Forward
Bit 1: Run Reverse
Bit 2 ~ Bit 15: Refer to the chapter 4.6.2 of this manual.
Examples:
Run Forward Command (Inverter Node Address: 01)
Command String (hexadecimal): 01 06 25 01 00 01 12 C6
Run Reverse Command (Inverter Node Address: 01)
Command String (hexadecimal): 01 06 25 01 00 03 93 07
Stop Command (Inverter Node Address: 01)
Command String (hexadecimal): 01 06 25 01 00 00 D3 06
Note:
The last 2 bytes of the command strings consist of a CRC16 checksum, please refer to section 4.5 of the instruction manual for
additional information.
318
VDI100 • Instruction manual