Wire size
mm
2
(AWG)
14 (6)
22 (4)
30 / 38 (3 /2)
50 / 60 (1/1/0)
70 (2/0)
80 (3/0)
100 (4/0)
3.7.

Wiring Peripheral Power Devices

After power is shut off to the inverter the capacitors will slowly discharge. Do NOT touch the inverter circuit
or replace any components until the "CHARGE" indicator is off.
Caution
Do NOT wire or connect/disconnect internal connectors of the inverter when the inverter is powered up or
after power off but the "CHARGE"" indicator is on.
Do NOT connect inverter output U, V and W to the AC power source. This will result in damage to the
inverter.
The inverter must be properly grounded. Use terminal E to connect earth ground and comply with local
standards.
It is required to disconnect the ground wire in the control board if the inverter is not grounded.
Do NOT perform a dielectric voltage withstand test (Megger) on the inverter this will result in inverter dam-
age to the semiconductor components.
Do NOT touch any of the components on the inverter control board to prevent damage to the inverter by
static electricity.
230V Class : 0.75~1.5 kW / 400V Class: 0.75~2.2 kW
Disconnect the ground wire of J1. on the control board (C/B).
VDI100 • Instruction manual
Terminal
Model of the round
screw size
crimp terminal
M4
R14-4
M5
R14-5
M6
R14-6
M8
R14-8
M6
R22-6
M8
R22-8
M6
R38-6
M8
R38-8
M8
R60-8
M10
R60-10
M8
R70-8
M10
R70-10
M10
R80-10
M16
R80-16
M10
R100-10
M12
R100-12
M16
R80-16
Model of insulating
Fastening torque
kgf.cm (in.lbs)
12.2 to 14 (10.4 to 12.1)
20.4 to 24 (17.7 to 20.8)
25.5 to 30.0 (22.1 to 26.0)
61.2 to 66.0 (53.0 to 57.2)
25.5 to 30.0 (22.1 to 26.0)
61.2 to 66.0 (53.0 to 57.2)
25.5 to 30.0 (22.1 to 26.0)
61.2 to 66.0 (53.0 to 57.2)
61.2 to 66.0 (53.0 to 57.2)
102 to 120 (88.5 to 104)
61.2 to 66.0 (53.0 to 57.2)
102 to 120 (88.5 to 104)
102 to 120 (88.5 to 104)
255 to 280 (221 to 243)
102 to 120 (88.5 to 104)
143 to 157 (124 to 136)
255 to 280 (221 to 243)
230V Class : 2.2~5.5 kW / 400V Class: 3.7~5.5 kW
Disconnect the ground wire of J1. on the control board (C/B).
Model of
sleeve
crimp tool
TIC 14
NH 1 / 9
TIC 14
NH 1 / 9
TIC 14
NH 1 / 9
TIC 14
NH 1 / 9
TIC 22
NOP 60/ 150H
TIC 22
NOP 60/ 150H
TIC 38
NOP 60/ 150H
TIC 38
NOP 60/ 150H
TIC 60
NOP 60/ 150H
TIC 60
NOP 150H
TIC 60
NOP 150H
TIC 60
NOP 150H
TIC 80
NOP 150H
TIC 80
NOP 150H
TIC 100
NOP 150H
TIC 100
NOP 150H
TIC 80
NOP 150H
21