feedback loss warning message "Pb" will be displayed on the keypad and the inverter will continue to operate.
10-11=2: Fault
A feedback loss condition is detected when the PID feedback value falls below the value set in parameter 10-
12 (PID feedback loss detection level) for the time set in parameter 10-13 (PID feedback loss detection time).
PID feedback loss fault message "Pb" will be displayed on the keypad, the inverter stops and the fault contact
is activated.
Code
Parameter Name / Range
10-17
Start frequency of PID sleep
0.00~599.00 Hz
10-18
Delay time of PID sleep
0.0~255.5 s
10-19
Frequency of PID wakeup
0.00~599.00 Hz
10-20
Delay time of PID wakeup
0.0~255.5 s
10-29
PID sleep selection
0: Disable
1: Enable
2: Set by DI
10-40
Selection of PID Sleep Compensation Frequency
0: Disable
1: Enable
The PID Sleep function is used to stop the inverter when the PID output falls below the PID sleep level (10-17)
for the time specified in the PID sleep delay time parameter (10-18).
The inverter wakes up from a sleep condition when the PID output (Reference frequency) rises above the PID
wake-up frequency (10-19) for the time specified in the PID wake-up delay time (10-20).
Use parameter 10-29 to enable / disable PID sleep function.
10-29 =0: PID Sleep function is disabled.
10-29 =1: PID sleep operation is based on parameters of 10-17 and 10-18.
10-29 =2: PID sleep mode is enabled by multi-function digital input
Refer to figure 4.4.83 (a) and (b) for PID sleep / wakeup operation.
220
Figure 4.4.82 PID feedback loss detection
Feedback
Value
10-12
FBL
Detection
t1
10-13
t
t
10-13
VDI100 • Instruction manual