C. Automatically switch acceleration/deceleration time
When output frequency equals to the value of 00-25, it follows the value of 00-25 to automatically switch accel-
eration/deceleration time1 and time2. Please refer to the following Figure 4.4.8.
When output frequency Fout<00-25 : Acceleration/deceleration time = Acceleration time1/ decelera-
tion time 1(00-14 and 00-15).
When output frequency Fout ≥ 00-25 : Acceleration/deceleration time = Acceleration time4/ decelera-
tion time 4(00-23 and 00-24)
When 03-00~03-07 set to 10 (Acceleration/ Deceleration Time Selection 1) and 03-00~03-07 set to 3 (Ac-
celeration/ Deceleration Time Selection 2), the priority is higher than 00-25.
Code
Parameter Name / Range
00-18
Jog frequency
0.00~599.00 Hz
00-19
Jog acceleration time
0.1~6000.0 s
00-19
Jog deceleration time
0.1~6000.0 s
Jog acceleration time (00-19) is the time required to accelerate from 0 to 100% of maximum output frequency.
Jog deceleration time (00-20) is the time required to decelerate from 100 to 0% of maximum output frequency.
Motor 1: Maximum frequency is set by parameter 01-02 and Motor 2 Maximum frequency is set by parameter
01-16.
When run command selection is external terminal control (00-02=1) and the inverter uses the jog frequency
(00-18, default 6.0 Hz) as its frequency reference with 03-00~03-07=6 or 7(6: Forward jog run command 7:
Reverse jog run command).The motor will run by the setting.
VDI100 • Instruction manual
Figure 4.4.8 automatically switch Acceleration/Deceleration time
Output
Frequency
00 - 25
Tacc1
Tacc4
Rate
Rate
( 00 - 14 )
( 00 - 23 )
time
Tdec4
Tdec1
Rate
Rate
( 00 - 15 )
( 00 - 24 )
103