gefran VDI100 Series Instruction Manual page 249

General purpose full vector inverter
Hide thumbs Also See for VDI100 Series:
Table of Contents

Advertisement

00040 - 09999: □□□□ (Integer only e.g. 1000 )
10001 - 19999: □□□. □ (1 decimal place e.g. 10.0)
20001 - 29999: □□. □□ (2 decimal places, e.g. 10.00)
30001 - 39999: □. □□□ (3 decimal places, e.g. 10.000)
<example>
16-03
00040
09999
10001
19999
20001
29999
30001
39999
Code
Parameter Name / Range
16-05
LCD backlight
0~7
Adjust the screen contrast of the digital operator. If it is set to 0, the screen backlight is turned off.
Code
Parameter Name / Range
16-07
Copy function selection
0: Do not copy parameter
1: Read inverter parameters and save to the keypad
2: Write the keypad parameters to inverter
3: Compare parameters of inverter and keypad
16-08
Selection of allowing reading
0: Do not allow to read inverter parameters and save to the keypad
1: Allow to read inverter parameters and save to the keypad
LCD digital operator with built-in memory (EEPROM) can be used to store and retrieve parameters:
(1) Read: Save inverter parameters to the digital operator (INV → OP).
(2) Write: Write the parameters from the digital operator to the inverter and save (OP → INV).
(3) Verify: Compare the inverter parameters against the parameters in the digital operator.
16-07=0: No action
16-07=1: Read (all parameters are copied from the inverter to the keypad).
16-07=2: Write (all parameter are copied from the keypad to the inverter).
16-07=3: Verify (Compare the set value of the inverter to the parameter of the digital operator).
Set 16-08 = 0, to prevent the saved parameter data stored in the digital operator from accidentally being over-
written.
VDI100 • Instruction manual
Display
Display unit
Example:
100 % speed is 0200
□□□□
> set 16-03=00200 (from 05-01, 06-01 to 06-15, set range from 0040 to 9999).
> set 16-04=0 (no unit)
Example:
100 % speed is 200.0 CFM
□□□. □
> set 16-03=12000 (05-01, 06-01 to 06-15, set range from 0000 to 9999).
> set 16-04=2 (CFM)
> 60% speed will be displayed as 120.0 CFM
use 16-04
Example:
setting
100 % speed is 65.00ºC
□□. □□
> set 16-03=26500 (05-01, 06-01 to 06-15, set range from 0000 to 9999)
> set 16-04=20 (ºC)
> 60% of speed is displayed as 39.00 ºC
Example:
100 % speed is 2.555 m/s
□. □□□
> set 16-03=32555
> set 16-04=14 (m/s)
> 60% speed is displayed as 1.533 m/s
Display example
249