gefran VDI100 Series Instruction Manual page 161

General purpose full vector inverter
Hide thumbs Also See for VDI100 Series:
Table of Contents

Advertisement

Function
Detection operation of frequency confirmation
03-14
Output
Frequency
Output frequency
Output
detection 2
Frequency
Detection 2
Signal
ON
Output
Frequency
Output frequency
detection 3
Output
Frequency
Detection 1
Signal
OFF
Output
Frequency
Output frequency
Output
detection 4
Frequency
Detection 1
Signal
OFF
Output
Frequency
Output frequency
Output
detection 5
Frequency
Detection 1
Signal
OFF
Output
Frequency
Output frequency
Output
detection 6
Frequency
Detection 2
Signal
ON
VDI100 • Instruction manual
03-13
03-13
03-14
03-13
OFF
ON
OFF
03-45
03-44
03-44
03-45
03-44
ON
OFF
ON
03-45
03-44
03-44
03-45
03-44
ON
OFF
ON
03-47
03-47
03-46
03-47
03-46
ON
OFF
ON
03-47
03-46
03-46
03-47
03-46
OFF
ON
OFF
Output is active when the output frequency is below the frequency
detection level (03-13) + frequency detection width (03-14) and
time
turns off when the output frequency falls below frequency detection
level.
03-13
Any of the digital outputs function (03-11, 03-12 or 03-28) can be
set to 5 (Output frequency detection 2).
ON
time
Output is active when the output frequency rises above the frequen-
cy detection level 2(03-44) + frequency detection width 2(03-45)
and deactivates when the output frequency falls below frequency
time
detection level 2(03-44).
03-44
Any of the digital outputs function (03-11, 03-12 or 03-28) can be
set to 50 (Output frequency detection 3).
time
Output is active when the output frequency is below the frequency
detection level 2(03-44) + frequency detection width 2(03-45) and
time
turns off when the output frequency falls below frequency detection
level 2(03-44).
03-44
Any of the digital outputs function (03-11, 03-12 or 03-28) can be
set to 51 (Output frequency detection 4).
time
Output is active when the output frequency rises above the frequen-
cy detection level 3(03-46) + frequency detection width 3(03-47)
time
and deactivates when the output frequency falls below frequency
detection level 3(3-46).
03-46
Any of the digital outputs function (03-11, 03-12 or 03-28) can be
set to 52 (Output frequency detection 5).
time
Output is active when the output frequency is below the frequency
detection level 3(03-46) + frequency detection width 3(03-47) and
time
turns off when the output frequency falls below frequency detection
level 3(03-46).
03-46
Any of the digital outputs function (03-11, 03-12 or 03-28) can be
set to 53 (Output frequency detection 6).
ON
time
Description
161