Step 5: Make connections and place filter cover back
3.6.

Wire Gauges and Tightening Torque

To comply with UL standards, use UL approved copper wires (rated 75° C) and round crimp terminals (UL List-
ed products) as shown in table below when connecting to the main circuit terminals. Gefran recommends using
crimp terminals manufactured by NICHIFU Terminal Industry Co., Ltd and the terminal crimping tool recom-
mended by the manufacturer for crimping terminals and the insulating sleeve.
Wire size
mm
2
(AWG)
0.75 (18)
1.25 (16)
2 (14)
3.5 / 5.5 (12/10)
8 (8)
20
Step 3: Unscrew filter section
Terminal
Model of the round
screw size
crimp terminal
M3.5
R1.25-3.5
M4
R1.25-4
M3.5
R1.25-3.5
M4
R1.25-4
M3.5
R2-3.5
M4
R2-4
M5
R2-5
M6
R2-6
M4
R5.5-4
M5
R5.5-5
M6
R5.5-6
M8
R5.5-8
M4
R8-4
M5
R8-5
M6
R8-6
M8
R8-8
Step 4: Remove filter cover
Step 6: Fasten screw
Model of insulating
Fastening torque
kgf.cm (in.lbs)
8.2 to 10 (7.1 to 8.7)
12.2 to 14 (10.4 to 12.1)
8.2 to 10 (7.1 to 8.7)
12.2 to 14 (10.4 to 12.1)
8.2 to 10 (7.1 to 8.7)
12.2 to 14 (10.4 to 12.1)
22.1 to 24 (17.7 to 20.8)
25.5 to 30.0 (22.1 to 26.0)
12.2 to 14 (10.4 to 12.1)
20.4 to 24 (17.7 to 20.8)
25.5 to 30.0 (22.1 to 26.0)
61.2 to 66.0 (53.0 to 57.2)
12.2 to 14 (10.4 to 12.1)
20.4 to 24 (17.7 to 20.8)
25.5 to 30.0 (22.1 to 26.0)
61.2 to 66.0 (53.0 to 57.2)
Model of
sleeve
crimp tool
TIC 1.25
NH 1
TIC 1.25
NH 1
TIC 1.25
NH 1
TIC 1.25
NH 1
TIC 2
NH 1 / 9
TIC 2
NH 1 / 9
TIC 2
NH 1 / 9
TIC 2
NH 1 / 9
TIC 5.5
NH 1 / 9
TIC 5.5
NH 1 / 9
TIC 5.5
NH 1 / 9
TIC 5.5
NH 1 / 9
TIC 8
NOP 60
TIC 8
NOP 60
TIC 8
NOP 60
TIC 8
NOP 60
VDI100 • Instruction manual