Fault Messages; Alarms - RMG EC 900 Operating Instructions Manual

Compact gas volume corrector
Table of Contents

Advertisement

..........................................................................................................................................................................................................

Fault messages

Alarms

No.
DSfG No.
1
783
2
30
3
31
4
32
5
1
6
2
7
3
8
104
9
105
10
416
11
427
12
415
13
429
14
428
15
405
16
409
17
406
18
424
19
410
20
414
21
4400
22
409
..........................................................................................................................................................................................................
Display of the EC 900
A
10-1
MU restart
A
11-0
p failure
A
11-1
p min range
A
11-2
p max range
A
15-0
t failure
A
15-1
t min range
A
15-2
t max range
A
17-4
Qb min range
A
17-5
Qb max range
A
21-5
1 out of 3 Vb1
A
21-6
1 out of 3 VmL1
A
21-7
1 out of 3 Vm1
A
23-1
1 out of 3 Vb1D
A
23-3
1 out of 3 Vm1D
A
31-0
RAM error C
A
31-1
RAM error F
A
31-2
RAM error O
A
31-3
RAM error N
A
32-0
Float error
A
32-1
Mathem. error
A
37-0
Tamper contact
A
10-3
Power failure
Explanation
Watchdog or short power failure of the EC 900
Failure of the pressure transmitter
Minimum pressure range value violated downwards
Maximum pressure range value exceeded
Failure of the temperature transmitter
Minimum temperature range value violated downwards
Maximum temperature range value exceeded
Min. range val. of flow rate at meas. cond. violated downw.
Max. range val. of flow rate at meas. cond. exceeded
1-out-of-3 comparison error, Vb1 totalizer
1-out-of-3 comparison error, VmLocal1 totalizer
1-out-of-3 comparison error, Vm1 totalizer
1-out-of-3 comparison error, Vb1D totalizer
1-out-of-3 comparison error, Vm1D totalizer
Error during RAM check, calibration parameters
Error during RAM check, factory parameters
Error during RAM check, operating parameters
Error during RAM check, general parameters
Error of floating-point arithmetic
Error in mathematics
Tamper contact has been initiated
Power failure
OPERATION
113

Hide quick links:

Advertisement

Table of Contents
loading