5 Display / WBM Configuration
5.2.9.2

Events

WBM: "Events" Tab
On this page, you specify how the IE/AS-i LINK reacts to system events and to
which. By selecting the corresponding check box, you specify which events cause
which reactions from the IE/AS-i LINK. The following options are available:
S The IE/AS-i LINK sends an E-mail.
S The IE/AS-i LINK triggers an SNMP trap.
S The IE/AS-i LINK saves the event in the diagnostic buffer.
Parameter
E-mail:
Enables/disables the sending of an E-mail when the corresponding event occurs.
To use this service, port 25 of the relevant server must be opened.
Trap
Enables/disables the triggering of an SNMP trap when the corresponding event
occurs.
To use this service, port 162/UDP of the relevant server must be opened.
Diagnostic buffer
Enables/disables the saving of the event in the diagnostic buffer.
The "E-mail" and "SNMP trap" options can only be enabled here if you made the
appropriate entries (addresses etc.) on the "Ethernet" page, "E-mail" or "SNMP"
tabs earlier (see Section 5.2.9.3 and 5.2.9.4).
Notice
Avoiding message storms
After a message has arrived (event: for example, slave failure), a new message is
triggered at the earliest after 3 seconds. If changes occur quickly, intermediate
statuses can therefore be lost.
IE/AS−INTERFACE LINK PN IO
70
Function
as of hardware version 1, as of firmware version V2.0
Release 08/2018
C79000−G8976−C216−03