Maintenance Events - Siemens SIMATIC 6DL1131-6DF00-0PK0 Equipment Manual

Table of Contents

Advertisement

Parameters, diagnostics messages and address space
A.4 Maintenance events
switched off. For diagnostic messages which refer to individual channels, only the
corresponding digital input is affected.
Diagnostics
Error
message
code
Wire break
6
H
Parameter as‐
10
H
signment error
Supply voltage
11
H
missing
Channel/compo‐
1F
H
nent temporarily
unavailable
Hardware inter‐
16
H
rupt lost
Module is faulty
100
H
Retentive memo‐
154
H
ry in carrier mod‐
ule defective
Retentive memo‐
155
H
ry in the terminal
block defective
47 kΩ resistors can be used provided that the following supplementary conditions are complied with: Only singular structure
1
of the IO modules (no IO redundancy); the process cables are shielded; no certification required according to the following
standards: NE21 or Power Station 6100-6-5.
Only the terminal blocks (TB 45 ...) are suitable for use of IO modules in IO redundancy.
2
A.4

Maintenance events

Maintenance events
A maintenance event is generated whenever maintenance is required. The MT LED lights up on
the module.
38
Assignment
Meaning
Digital input
Impedance of encoder circuitry is too
high
Wire break between the module and
sensor
Channel not connected (open)
Module
Parameter assignment does not
match the terminal block used
Incorrect parameter assignment
Module
Missing or insufficient supply voltage
L+
Module
Update of the firmware is being per‐
formed or has been canceled.
The module does not import any
process values during this time.
Module
Error is reported because the events
occur faster than they can be pro‐
cessed in the system
Module
Internal module error has occurred
Module
A memory block fault on the support
module was detected during start-up
Module
A memory block fault on the terminal
block was detected during start-up
Solution
Use a different encoder type or
modify the wiring, for example,
using cables with a larger cross-
section
Connect the cable
Disable diagnostics
Connect encoder contacts
with a 15 kΩ to 18 kΩ resistor
Correct the parameter assign‐
ment
Check terminal block
Check wiring of the supply
voltage L+ on the terminal
block
Check the terminal block type
Restart firmware update
Wait for firmware update
Replace I/O module
Replace carrier module
Replace terminal block
DI 8x24...125VDC HA