Connectors For The As-I Cable(S) And Power Supply - Siemens SIMATIC NET IE/AS-INTERFACE LINK PN IO Manual

Table of Contents

Advertisement

1.7.1

Connectors for the AS-i Cable(s) and Power Supply

Caution
!
When connecting up the module, keep to the installation guidelines in Section 1.5.
Caution
!
The IE/AS-INTERFACE LINK PN IO may only be connected when the AS-i power
supply unit is turned off.
Connectors for the AS-i Cable(s)
The IE/AS-i LINK has two connectors for the AS-i cables (line 1 and line 2). Each
is connected over a 4-pin plug with two + and two − contacts that are jumpered
internally.
This allows the IE/AS-i LINK to be looped into the AS-i cable.
Caution
!
The permitted current loading of the AS-i connection contacts is 3 A. If this value
is exceeded on the AS-i cable, the IE/AS-INTERFACE LINK PN IO must not be
looped into the AS-i cable but must be connected with a tap line (only one pair of
connectors of the IE/AS-i LINK is used).
Pin assignment of the AS-i line
PIN no. line 1
1
2
3
4
Pins 1 and 3 and pins 2 and 4 are jumpered internally.
IE/AS−INTERFACE LINK PN IO
Release 08/2018
C79000−G8976−C216−03
1 Technical Description, Installation Guidelines, Operation
Signal
AS-i 1 +
AS-i 1 −
AS-i 1 +
AS-i 1 −
as of hardware version 1, as of firmware version V2.0
PIN no. line 2
Signal
1
AS-i 2 +
2
AS-i 2 −
3
AS-i 2 +
4
AS-i 2 −
21