Device-specific errors of the link for the "Status" return value
Table 8-3
Error Detection in "STATUS[4]" of the Return Value of the IE/AS-i LINK
STATUS[4]
01
Invalid CTT2 index
H
02
Invalid CTT2 length
H
04
CTT2 slave is temporarily busy.
H
05
The addressed AS-i slave was not found on the AS-Interface.
H
06
An AS-i slave with address 0 exists.
H
07
An AS-i slave with the new address already exists on the AS-Interface.
H
08
The AS-i slave address cannot be deleted.
H
09
Error reading the extended ID1 code
H
0A
The AS-i slave address cannot be set.
H
0B
The AS-i slave address cannot be stored permanently.
H
21
The AS-i slave address is incorrect
H
22
The AS-i slave is not activated (not in LAS).
H
23
Error on the AS-Interface
H
24
The call not permitted in the current status of the AS-i master.
H
25
An AS-i slave with address 0 exists.
H
26
The AS-i slave has illegal configuration data (I/O or ID codes).
H
27
The target address is not plausible (for example a B slave address was used for a
H
standard slave).
2E
The job number or the job parameter is unknown.
H
2F
The AS-i master has detected an EEPROM error.
H
31
A length error has occurred transferring a string.
H
32
A protocol error has occurred transferring a string.
H
33
CTT2 slave not initialized.
H
FF
Error not specified in greater detail
H
You will find other, general error IDs in the Help on SFB54.
IE/AS−INTERFACE LINK PN IO
Release 08/2018
C79000−G8976−C216−03
as of hardware version 1, as of firmware version V2.0
8 Using the Data Record Interface
Meaning
123

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SIMATIC NET IE/AS-INTERFACE LINK PN IO and is the answer not in the manual?

Questions and answers

Table of Contents