Read_AS-i_Slave_Errorcounters

Meaning
This call reads out AS-i slave-specific error counters.
The data record can be requested by the PROFINET IO controller.
Meaning of the counters:
Slave failure
Missing slave frame
Bad slave frame
Protocol error
Bad master frame (optional)
Structure of the RecordDataRead service − Index 98
Byte
Bit 7
Bit 6
0
1
2
3
4
5
6
7
8
9
10
11
12
13
IE/AS−INTERFACE LINK PN IO
Release 08/2018
C79000−G8976−C216−03
Error
The slave was taken out of the list of activated slaves
Slave response of an existing slave was not received.
I/O error
Error in data transfer according to CTT1−5 (for example,
AS-i master detects an error in its own send frame (by
Bit 5
Bit 4
Version_hi = 0x00
Version_lo = 0x00
Slave failure
Missing slave frame
Bad slave frame
Protocol error
Bad master frame
as of hardware version 1, as of firmware version V2.0
8 Using the Data Record Interface
Meaning
(LAS) (after several consecutive timeouts).
Slave response of a slave is mutilated or corrupt.
Slave signals "Peripheral Fault" in the response to
Read_Status.
bad or missing toggle bit, ...).
checking the receive line).
Meaning
Bit 3
Bit 2
I/O error
Bit 1
Bit 0
High byte
Low byte
High byte
Low byte
High byte
Low byte
High byte
Low byte
High byte
Low byte
High byte
Low byte
173

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SIMATIC NET IE/AS-INTERFACE LINK PN IO and is the answer not in the manual?

Questions and answers

Table of Contents