Uninterruptible Power Supply (Ups); Ac Input Power For Modular Cabinets; North America/Japan Single-Phase Power Specifications - HPE Integrity NonStop NS2100 Planning Manual

Table of Contents

Advertisement

voltage of AC power at the intended installation site for the system. For information on the PDUs
supported for an NS2100 system, see

Uninterruptible Power Supply (UPS)

An NS2100 system can use the HPE model R5000 UPS for a single-phase power configuration
or the HPE model R12000/3 UPS for a three-phase power configuration. An extended run-time
module (ERM) can be combined with a UPS to extend battery time. For more information, see
"Uninterruptible Power Supply (UPS)" (page

AC Input Power for Modular Cabinets

This subsection provides information about AC input power for NS2100 modular cabinets.
Table 2 (page 58)
used in North America and Japan.
Table 3 (page 59)
used in North America and Japan.
Table 4 (page 59)
used in international installations.
Table 5 (page 59)
used in international installations.
CAUTION:
within the system do not exceed the capacity of the branch circuit according to applicable electrical
codes and regulations.
Select circuit breaker ratings according to local codes and any applicable regulations for the
circuit capacity. Note that circuit breaker ratings vary if your system includes an optional
rack-mounted UPS.
Table 2 North America/Japan Single-Phase Power Specifications
Output Load
Input Voltage
Input Connector
Output Voltage
Output Connectors
Notes
58
System Installation Specifications for NS2100 Systems
contains the single-phase power specifications for the power components
contains the single-phase power specifications for the power components
contains the single-phase power specifications for the power components
contains the single-phase power specifications for the power components
Be sure the hardware configuration and resultant power loads of each cabinet
R5000 1-phase UPS
4500 W
200 – 208 V
NEMA L6-30P
200 – 208 V
1 x L6-30R
4 x C19
4 x C13
UPS outputs are connected to the compatible PDU inputs.
"AC Input Power for Modular Cabinets" (page
40).
iPDU 1-phase
24 A
200 – 208 V
NEMA L6-30P
N/A
6 x C19
(20 x C13)
58).
Modular PDU 1-phase
24 A
200 – 240 V
NEMA L6-30P
N/A
4 x C19
(28 x C13)