2.4.2
Installation of box-type reactor (FR-XCB)
Clearances
Installation place
Install the reactor on nonflammable material. Installing it directly on flammable material will cause a fire.
Surrounding environment
Avoid places where the equipment is subjected to oil mist, flammable gases, fluff, dust, dirt, etc.
Install the equipment in a clean place or protect it from suspended substances.
Installation orientation
Install the reactor on a vertical surface.
Wiring method
Make cuts in rubber bushes on the bottom of the reactor and lead the wires through the cuts.
NOTE
• To satisfy IP20 protection requirements, note the following points for wiring of the reactor.
- Do not make cuts in rubber bushes which are not used for wiring.
- Do not use the reactor with the rubber bushes removed.
10 cm or more
5 cm or more
10 cm or more
Installation of peripheral devices
5 cm or more
Vertical